EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204
page 50 of 86
-32768 32767 - - - 0
value of the password to gain access to
level 5
Password Level 5:
- - - - - - - - - ON
enabling the password to gain access to
level 5
OFF = to gain access to level 5 one
has not to set any password
ON = to gain access to level 5 one
has to set a password
Password Timeout 0 240 s 240
time-out of the passwords to gain access to
the levels (after this time since the last
operation with the buttons, to gain access to
the level one has to set a password again, if
foreseen)
Diagnostic FRAM parameter available in read only modality
non volatile memory status
ok = not in error
err = in error
Diagnostic RTC parameter available in read only modality
clock status
ok = not in error
err = in error
low = loss of data
Diagnostic STACK parameter available in read only modality
stack status
ok = not in error
err = in error (because of overflow)
Diagnostic Power Supply parameter available in read only modality
power supply voltage status
ok = not in error
err = in error (because of out of
range voltage)
Diagnostic 5V Ratio parameter available in read only modality
status of the power supply voltage of the
ratiometric transducers
ok = not in error
err = in error (because of out of
range voltage)
Diagnostic 24V Sensor parameter available in read only modality
status of the power supply voltage of the
0-20 mA / 4-20 mA / 0-10 V transducers
ok = not in error
err = in error (because of out of
range voltage)

Table of Contents