Par. Description MU Range Default
r12
Differential position r0.
0=Asymmetrical;
1 = Symmetrical.
--- 0/1 0
COMPRESSOR Group
C0 Compressor ON delay from power-on. min 0...240 0
C2 MinimumcompressorOFFtime. min 0...240 3
C3 Minimum compressor ON time. s 0...240 0
C4 CompressorOFFtimeincabinetprobealarm. min 0...240 10
C5 Compressor ON time in cabinet probe alarm. min 0...240 10
C6 Condensation temperature above which the condenser overheat alarm sounds. °C/°F 0.0...199 80.0
C7
Condensertemperatureabovewhichthecompressorlockedalarmsounds,onceC8 time
has elapsed.
°C/°F 0.0...199 90.0
C8
DelayinactivationofcompressorlockedalarmduetothresholdC7 being exceeded.
min 0...15 1
C10 Compressor hours for maintenance. 0 = Disabled. h 0...999*100 0
C11 Second compressor switch-on delay from first compressor switch-on. s 0...240 10
C13 Number of start-ups per compressor rotation. 0 = Disabled. num 0...10 0
DEFROST Group
d0 Defrost interval. 0 = Manual defrost only. If d8=3,maximuminterval. h 0...99 8
d1
Type of defrost.
0 = Electrical heaters;
1 = Cycle reversed (hot gas);
2 = When compressor stops.
--- 0...2 0
d2 Evaporation temperature above which defrost with evaporator probe terminates (Pr3 = 5). °C/°F -99.0...99.0 8.0
d3 Defrost duration. If P3=1,maximumduration. min 0...99 30
d4
Enable defrost when device is switched on.
0 = Disabled;
1 = Enabled.
--- 0/1 0
d5 Defrost activation delay from power-on. min 0...99 0
d6
Value displayed during defrost.
0 = Regulation;
1=Lockeddisplay;
2=Code"DEF".
--- 0...2 1
d7 Evaporator dripping time after defrost. min 0...15 0
d8
Defrost interval count mode.
0 = Hours device ON;
1 = Hours compressor ON;
2 = Hours evaporator temperature < d9;
3=Adaptive;
4 = In real time (RTC).
--- 0...4 0
d9 Evaporation threshold for automatic defrost interval count. °C/°F -99.0...99.0 0.0
d11
Enable defrost terminated warning due to maximum duration (code dFd)
.
0 = No; 1 = Yes.
--- 0/1 0
d15 Compressor ON time before hot gas defrost. min 0...99 0
d16 Pre-dripping time for hot gas defrost. min 0...99 0
d18 Adaptivedefrostinterval.0 = Manual defrost only. min 0...999 40
d19 Adaptivedefrostthreshold(relativetooptimalevaporationtemperature). °C/°F 0.0...40.0 3.0
d20 Compressor-on consecutive time for defrost. min 0...999 180
d21 Compressor-on consecutive time for defrost from power-on and from over-cooling. min 0...500 200
d22
Evaporation threshold for adaptive defrost interval count (relative to optimal evaporation
temperature).
°C/°F -10.0...10.0 -2.0
ALARM Group
AA
Select value for high/low temperature alarms
0 = Regulation temperature;
1 = Evaporator temperature;
2 = Probe Pb3 temperature.
--- 0...2 0
A1 Lowtemperaturealarmthreshold. °C/°F -99.0...99.0 -10.0