d8 0 4 - - - - 0 0 0 0 0 0 0 0
defrosting activation methods
0
=
AT INTERVALS - defrosting will be activated once
the device has altogether been running for time
d0
1
=
AT INTERVALS - FOR COMPRESSOR SWITCH-ON -
defrosting will be activated once the compressor
has altogether been switched on for time d0
2
=
AT INTERVALS - FOR EVAPORATOR TEMPERATURE
- defrosting will be activated when the evaporator
temperature has remained below the temperature
d9 for a total time of d0 (17)
3
=
ADAPTABLE - defrosting will be activated at
intervals, whose duration will each time depend
on the duration of compressor switch-ons and the
evaporator temperature; see also d18, d19, d20
and d22 (17)
4
=
IN REAL TIME - defrosting will be activated at the
times established in parameters Hd1... Hd6 (not
visible in models EVB1204, EVB1206, EVB1226
and EVB1246)
d9 -99 99.0
°C/°F
(1)
0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
evaporator temperature is higher than that at which the
defrost interval counter is suspended (only if d8 = 2)
d11 0 1 - - - - 0 0 0 0 0 0 0 0
defrosting alarm switches off once maximum time limit
has been reached (code dFd”; only if P3 = 1 and in
absence of an evaporator temperature probe (code “Pr2”)
1
=
YES