16 ERRORS
16.1 Errors
The following table shows the meaning of the error codes of the device.
CODE MEANING
Pr1
room temperature/inlet air temperature probes error
Solutions:
-
check that the probe is the PTC, NTC or Pt 1000 type; see parameter P0
-
check the device-probe connection
-
check room/inlet air temperature
Main consequences:
-
compressor activity will depend on parameters C4 and C5
-
the defroster will not be activated
-
the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
-
the door heating elements will be switched off (only and provided parameter u1 and/or parameter u11 is set
at 4)
-
the neutral area operating heating elements will be deactivated (only if parameter u1 and/or parameter u11
is set at 5)
-
if parameter P4 is set at 3, the temperature associated to regulation will be that detected by the outlet air
temperature probe
Pr2
Evaporator temperature probe error
Solutions:
-
the same as the preceding case but with respect to the evaporator temperature probe
Main consequences:
-
if parameter P3 is set at 1, the defrosting period will last for the amount of time set with parameter 3
-
if parameter P3 is set at 1and parameter d8 is set at 2 or to 3, the device will operate as if parameter d8
were set at 0
-
if parameter F0 is set at 3 or 4, the device will operate as if the parameter were set at 2
-
the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
Pr3
Auxiliary temperature probe error
Solutions:
-
the same as in the previous example, but with regard to the auxiliary temperature probe
Main consequences:
-
if parameter P4 is set at 1:
-
condenser overheated alarm (codeCOH”) will never be activated
-
he compressor blocked alarm (code “CSd) will never be activated
-
the condenser fan will operate parallel to the compressor (only if parameter u1 and/or
parameter u11 is set at 6)
-
the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
-
if parameter P4 is set at 3, the temperature associated to regulation will be that detected by the inlet air
temperature probe
Pr4
Evaporation temperature probe error
Solutions:
-
the same as in the previous example, but with regard to the evaporation temperature probe
Main consequences:
-
the electronic expansion valve will be open the percentage set with parameter h17
-
the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)