Pr5
Evaporation pressure probe error
Solutions:
-
check that the probe is the 4-20 mA type
-
check the device-probe connection
-
check the vapour pressure
Main consequences:
-
the electronic expansion valve will be open the percentage set with parameter h17
-
the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
Pr7
Auxiliary 2 temperature probe error
Solutions:
- check that the probe is the NTC or Pt 1000 type; see parameter Sd6
-
check the device-probe connection
-
check auxiliary 2 temperature
Main consequences:
- the device will record the error
-
the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
Pr8
Auxiliary 3 temperature probe error
Solutions:
- the same as in the previous example, but with regard to the auxiliary 3 temperature probe
Main consequences:
- the device will record the error
-
the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)
FUL
Error SD card space run out
Solutions:
- get free space on the SD card or replace it
Main consequences:
- the device will not write information
Sd
Error SD card not inserted or not recognized
Solutions:
- insert the SD card or replace it
Main consequences:
- the device will not write information
BAt
Data logger battery error
Solutions:
- check the battery is charged
Main consequences:
- the device will not write information