EVBOX1 | Installation guide ver. 2.0 | Code 144BOX1E204
page 73 of 100
u2 0 1 - - - - 0 0 0 0 0 0 0 0
activation of room light switch on/off (in models EVB1204
and EVB1214 only if u1 = 0) or of the auxiliary output (in
models EVB1204 and EVB1214 only if u1 = 2, in the
remaining models only if u1 and/or u11 = 2) in manual
mode with the device turned off (40).
1
=
YES
u3 0 240 s 10 10 10 10 10 10 10 10
if C14 = 0 compressor switch-off delay after pump down
valve switch-off
if C14 = 1 or 2, maximum delay between pump down
valve switch-off and compressor switch-off
u4 0 1 - - - - 1 1 1 1 1 1 1 1
enabling of alarm output deactivation with the silencing of
the buzzer (in models EVB1204 and EVB1214 only if u1 =
3, in the remaining models only if u1 and/or u11 = 3)
1
=
YES
u5 -99.0 99.0
°C/°F
(1)
-1.0 -1.0 -1.0 -1.0 -1.0 -1.0 -1.0 -1.0
room temperature or CPT temperature below which the
door heating elements are turned on ("u5 - 2.0°C/4°F in
models EVB1204 and EVB1214 only if
u1 = 4, in the remaining models only if u1 and u11 = 4).
u6 1 120 min 5 5 5 5 5 5 5 5
duration of demister heating elements activation (in
models EVB1204 and EVB1214 only if u1 = 1, in the
remaining models only if u1 and/or u11 = 1)
u7 -99.0 99.0
°C/°F
(1)
-5.0 -5.0 -5.0 -5.0 -5.0 -5.0 -5.0 -5.0
neutral area value (relative to the work set-point, i.e.
“work set-point + u7) (in models EVB1204 and EVB1214
only if u1 = 5, in the remaining models only if u1 and/or
u11 = 5) (41)