EVCO S.p.A.
EVBOX1 | Installation guide ver. 2.0 | Code 144BOX1E204
page 83 of 100
AUX1
and
AUX2
Auxiliary LED 1 and Auxiliary LED 2
If the LED is on:
-
the demister heating elements will be switched on (only if the parameter u1 and/or parameter u11 is set at
1)
-
the auxiliary output will have been switched on in manual mode (only if the parameter u1 and/or parameter
u11 is set at 2)
-
the door heating elements will be switched on (only if the parameter u1 and/or parameter u11 is set at 4)
-
the neutral area operating heating elements will be activated (only if the parameter u1 and/or parameter
u11 is set at 5)
-
the condenser fan will be on (only if the parameter u1 and/or parameter u11 is set at 6)
-
compressor 2 will be on (only if the parameter u1 and/or parameter u11 is set at 7)
-
the defrosting output 2 will be on (only if the parameter u1 and/or parameter u11 is set at 8)
-
evaporator 2 fan will be on (only if the parameter u1 and/or parameter u11 is set at 9)
-
the pump down valve will be on (only if the parameter u1 and/or parameter u11 is set at 10)
-
the on/stand-by output will be on (only if the parameter u1 and/or parameter u11 is set at 11)
-
the man in cold room output will be on (only if the parameter u1 and/or parameter u11 is set at 12)
If the LED is flashing:
- compressor 2 protection will be in progress; see parameters C0, C1, C2, C11 and i7
- evaporator fan 2 standstill will be in progress; see parameter F3
-
the auxiliary out put will have been switched on from a digital input; see parameters i5 and i15 (only if the
parameter u1 and/or parameter u11 is set at 2)
Clock LED light
If the LED is on:
-
the value displayed shall be a time
If the LED is flashing:
-
the date, time and day of the week are being set
temperature LED light
If the LED is on:
-
the value displayed shall be a temperature
If the LED is flashing:
-
the “rapid cooling” function is in progress; see parameters r5 and r6
pressure LED light
If the LED is on:
-
the value displayed shall be a pressure
HACCP
HACCP LED light
If the LED is on:
-
not all the information on the HACCP alarms has been displayed
If the LED is flashing:
-
if it is flashing, the device has saved at least one new HACCP alarm
Energy saving LED light
If the LED is on:
-
the “energy saving” function is in progress

Table of Contents