The I²t protection of the drive went off. The duty cycle is greater than the system can
provide. Decrease the speed overshoot in the system response.
There is short-circuit at the drive module. Reset the error. If it persists, may be because:
An erroneous sequence when connecting the power cables or a short-circuit between
them.
The parameters may be wrong or there is a fault at the drive.
Contact Fagor Automation.
After displaying E.214, one of the codes of the following table will be displayed.
The drive where the alarm has been detected is:
The hardware of the drive module detects that the voltage at the power bus is too high.
When using an external Ballast, it is not connected properly. The Ballast resistor is
burned.
Disconnect the power supply and check the proper connection of the Ballast circuit.
The mains voltage is too low.
Disconnect the power supply and check the proper condition of the lines.
E.214 Short-circuit
1L The 1st one of the bottom 3L The 3rd one of the bottom
1H The 1st one of the top 3H The 3rd one of the top
2L The 2nd one of the bottom CR That of the Ballast
2H The 2nd one of the top
E.304 Power bus voltage of the drive too high
E.307 Power bus voltage too low
E.201
Time
KV36
TV2
MP3
f(MP3)
E.202
Time
KV32
CV3
Drive
Nominal
Current
f(drive
nominal
current)