- 11 -
11
Communication Protocols
1- 2. Structure of Frame type (Ver6)
1-2-1.Frame type and Data Configuration
(1) The following table explains the content and configuration by frame type of data.
Frame
Type
Library Name
Contents
0x01
(1)
FAS_
GetSlaveInfo
Connected slave type and program version information are required.
Sending : 0 byte
Response : 1~248 bytes
1 byte
1 bytes
0~246 bytes
Communication
status
Slave type
ACII string with NULL byte
( strlen() + 1 byes)
♦ Slave type : 20 : Ezi-STEP Plus-R ST 60 : Ezi-STEP Plus-R MINI
1 : Ezi-SERVO Plus-R ST
0x05
(5)
FAS_
GetMotorInfo
Connected motor type and manufacturer information are required.
Sending : 0 byte
Response : 1~248 bytes
1 byte
1 bytes
0~246 bytes
Communication
status
Motor type
(1~255)
ACII string with NULL byte
( strlen() + 1 byes)
♦ Motor type: refer to 「1-1-7.Information of Motors」
0x10
(16)
FAS_
SaveAllParameters
Save currently set parameters & assigned signals in the ROM o f the
drive. Even the drive is powered off, saving these data & parameters
are possible.
Values set at ‘FAS_SetParameter’ &‘FAS_SetIOAssignMap’ are saved
together.
Sending : 0 byte
Response : 1 byte
1 byte
Communication status
0x11
(17)
FAS_
GetROMParameter
Specific parameter values in the ROM are recognized.
Sending : 1 byte
1 byte
Parameter number (0~28)
Response : 5 bytes
Refer to 「1-2-2.Parameter List」
1 byte
4 bytes
Communication status
Parameter value