Quadnet Control Panel Engineering and Commissioning Manual
Important Points
• Use a 2-core 1.5mm
2
with screen fire rated cable as per the
specifications in “Cable Specification” and “Network Cable
Specification”.
• For each loop, connect all the devices in a complete loop (returning
from the last device to the control panel).
• Make sure that the cable screens are sleeved, connected together
and connected to the relevant connections at the control panel.
• Leave a copy of the User Instructions by the control panel, and make
sure that you have explained its operation carefully to the relevant
persons (the user, not the contractors or their agents).
• Do not remove devices or chambers in earlier devices with the loop
active – this could cause the system to go into full fire.
If you have any further queries, please contact your supplier for further information
0832
Fike Safety Technology Ltd
Unit 31, Springvale Ind. Est.
Torfaen, NP44 5BD
12
DoP-507-0001, DoP-507-0009
EN54-2: 1997 +A1: 2006, EN54-4: 1997 +A1: 2002 +A2:
2006
507-0001
Intended for use in the fire detection and fire alarm
Systems in and around buildings
Essential characteristics
Durability of operational reliability and
response delay, Temperature resistance
Pass
Durability of operational reliability,
Vibration resistance
Pass
Durability of operational reliability,
Humidity resistance
Pass
Durability of operational reliability,
Corrosion resistance
Pass
Durability of operational reliability,
Electrical stability
Pass
Performance under fire conditions
Response delay (response time to fire)
Performance of power supply
Contact your distributor for technical support
on this product.
Do not call the Fike Safety Technology technical
support department unless your distributor has first
given their advice and attempted to rectify the
issue.
Technical support will not be available if the
instruction manual has not been read and
understood. Please have this instruction manual
available whenever you call for technical support.