TWINFLEX
®
pro² Control Panel Engineering and Commissioning Manual
29
The Active Log will display any current fires. These are displayed in
text format and may be scrolled through by pressing the UP and
DOWN keys. Press the ESC key to exit the menu.
.
The Active Log will display any current faults. These are displayed in
text format and may be scrolled through by pressing the UP and
DOWN keys. Press the ESC key to exit the menu.
The Active Log will display any current disables. These are displayed
in text format and may be scrolled through by pressing the UP and
DOWN keys. Press the ESC key to exit the menu.
The Active Log will display any current warnings. These are displayed
in text format and may be scrolled through by pressing the UP and
DOWN keys. Press the ESC key to exit the menu.
The Test Display function causes the LCD screen to blacken and the
test LED to illuminate.
The Test LEDs function causes the panel LEDs to toggle on/off to test
for correct operation. When this option is active, the test light will be
illuminated.