TWINFLEX
®
pro² Control Panel Engineering and Commissioning Manual
30
The Test Buzzer function toggles on and off to ensure correct buzzer
operation unless the buzzer has been disabled by fitting a jumper link
to LK1 on the PCB. The test light will illuminate while this action is
taken.
The Test Keyboard function enables the user to select each button to
ensure the correct function is shown on the screen. Press the ESC key
TWICE to exit the menu.
The Silent Test function allows the selection of one or more detection-
zones to operate in a ‘silent one-man walk test mode’. On triggering a
device, the device LED operates, the sounder does not sound and the
control panel indicates an alarm. After approximately 5 seconds the
system will reset the device and another may be tested. The control
panel event log will indicate that a test mode has been selected. This
operation will also enable the test LED.
N.B. To put ALL zones into test, enter 00 for the zone number.
The Local Audible Test function allows the selection of one or more
detection-zones to operate in a ‘one-man walk test mode with local
sound’. On triggering a device, the device LED operates, the sounders
within that zone operate and the control panel indicates an alarm. After
approximately 5 seconds, the system will reset the device and another
may be tested. The control panel event log will indicate that a test
mode has been selected.
N.B. To put ALL zones into test enter 00 for the zone number.