TWINFLEX
®
pro² Control Panel Engineering and Commissioning Manual
31
The System Test function allows the entire system to operate in a
simple one-man walk test mode. On triggering a device the device LED
operates, all the assigned sounders operate for 10 seconds and the
control panel indicates an alarm. After approximately 10 seconds, the
system will reset the device and another may be tested. The control
panel event log will indicate that a test mode has been selected.
Please note that with the system test mode, only the sounders
assigned to operate from that device will sound and any delays will still
be present e.g. if a delay of 2 minutes is present, the system will have
been reset before the sounders activate.
N.B. To put ALL zones into test enter 00 for the zone number.
This function allows the global disablement or enablement of all fire
outputs on the panel. The control panel will indicate that disablements
are present and a disablement event will be recorded to log.
This function allows the global disablement or enablement of all the
sounders on the system. The control panel will indicate that
disablements are present and a disablement event will be recorded to
log.
This function allows output delays to be temporarily turned off.
This function allows the disablement or enablement of a detection
zone. Thus, all the input devices (Manual Call Points, detectors and
inputs) within that detection-zone will be disabled. The control panel
will indicate that disablements are present and a disablement event will
be recorded to log Automatic Detection devices will not activate, MCPs
will activate but no event will be recorded to log and no programmed
actions will occur. The sounder within the devices will still operate if
triggered from elsewhere on the system.