TWINFLEX
®
pro² Control Panel Engineering and Commissioning Manual
39
This function allows the global disablement or enablement of all fire
outputs on the panel. The control panel will indicate that disablements
are present and a disablement event will be recorded to log.
This function allows the global disablement or enablement of all the
sounders on the system. The control panel will indicate that
disablements are present and a disablement event will be recorded to
log.
This function allows the sounders to either re-sound on another alarm
or to remain in the silenced mode.
This function allows the disablement or enablement of a detection-
zone. Thus, all the input devices (Manual Call Points, detectors and
inputs) within that detection-zone will be disabled. The control panel
will indicate that disablements are present and a disablement event will
be recorded to log. Automatic Detection devices will not activate,
MCPs will activate but no event will be recorded to log, and no
programmed actions will occur. The sounder within the devices will still
operate if triggered from elsewhere on the system.
3. Enable/ Disable
1. Remote Fires
3. Enable/ Disable
2. All Sounders
3. Enable/ Disable
4. Zone
01/09/09 22:26 ENGR
REMOTE FIRE:DISABLED
1.DISABLE 2.ENABLE
Press <> OR Esc Key
01/09/09 22:26 ENGR
SOUNDERS:DISABLED
1.DISABLE 2.ENABLE
Press <> OR Esc Key
01/09/09 22:26 ENGR
ZONE(ENABLE/DISABLE)
ENTER ZONE:00
Press Enter Key
01/09/09 22:26 ENGR
ZONE: ENABLED
1.DISABLE 2.ENABLE
Press <> OR Esc Key
3. Enable/ Disable
3. Re-sound Sounders
Sounders
01/09/09 22:26 ENGR
OPTION : AUTOMATIC
1.MANUAL 2.AUTO
Press <> OR Esc Key
2. Test Modes
4. Test inputs
3. Monitored I/P
01/09/09 22:26 ENGR
MON I/P TESTING.
INPUT ACTIVATED
Press Enter Key
This will test monitored input and when it is triggered
INPUT ACTIVATED will be displayed on line 3 of the
display.
www.acornfiresecurity.com
www.acornfiresecurity.com