TWINFLEX
®
pro² Control Panel Engineering and Commissioning Manual
43
This active control will allow the engineer to set an alarm delay for the
panel fire relay. Use the LEFT and RIGHT keys to toggle through the
following options. Once the correct option has been selected, press the
ENTER key.
1. INSTANT – When the panel receives a fire input
the fire relay will immediately activate.
2. DELAYED – When the panel receives a fire input
the fire relay will be delayed for the
time period set in the ‘Delay Timer’
menu.
This active control will allow the engineer to set an alarm delay for
Monitored Output 1. Use the LEFT and RIGHT keys to toggle through
the following options. Once the correct option has been selected, press
the ENTER key.
1. INSTANT – When the panel receives a fire input
Monitored Output 1 will immediately
activate.
2. DELAYED – When the panel receives a fire input
Monitored Output 1 will be delayed for
the time period set in the ‘Delay Timer’
menu.
This active control will allow the engineer to set an alarm delay for
Monitored Output 2. Use the LEFT and RIGHT keys to toggle through
the following options. Once the correct option has been selected, press
the ENTER key.
1. INSTANT – When the panel receives a fire input
Monitored Output 2 will immediately
activate.
2. DELAYED – When the panel receives a fire input
Monitored Output 2 will be delayed for
the time period set in the ‘Delay Timer’
menu.
This active control will allow the engineer to set the alarm delay timer.
Press 0 – 5 to set the timer from No Delay to 5 Minutes, then press
ENTER to confirm the change. If a delay time is set, then the Delay
LED will be lit. Delayed zones or outputs will not be delayed if a zero
time is selected.