TWINFLEX
®
pro² Control Panel Engineering and Commissioning Manual
44
This active control will allow the engineer to automatically override any
delay in the zone of origin. Use the LEFT and RIGHT keys to toggle
through the following options. Once the correct option has been
selected press the ENTER key.
1. INSTANT – If any zone programmed with an
output delay enters an alarm
condition, the output delay on that
initiating zone will be cancelled. All
other zones will operate as per their
output delay settings.
2. SETTING – All zones will operate as per their
output delay settings.
This active control will allow the engineer to temporarily switch off the
panel buzzer whilst in engineer mode. When the user exits engineer
mode, the buzzer will be re-enabled. Use the LEFT and RIGHT keys to
toggle through the options, then press ENTER to confirm the change.
This active control will allow the engineer to change the code for
access to the user menus. Use the UP and DOWN keys to move the
cursor between options and the alphanumeric keypad to enter the
code. Press the ENTER key to confirm the change.
This active control will allow the engineer to change the code for
access to the supervisor menus. Use the UP and DOWN keys to move
the cursor between options and the alphanumeric keypad to enter the
code. Press the ENTER key to confirm the change.
This active control will allow the engineer to change the code for
access to the engineer menus. Use the UP and DOWN keys to move
the cursor between options and the alphanumeric keypad to enter the
code. Press the ENTER key to confirm the change.