TWINFLEX
®
pro² Control Panel Engineering and Commissioning Manual
53
This active control will allow the engineer to view or change the
operation of the disablement event set for monitored input. Use the UP
and DOWN arrow keys to toggle through the following options. To
confirm the changes press ENTER.
1. DISABLE SOUNDERS – Operation of I/P will disable
the sounders.
2. DISABLE REM.FIRE – Operation of I/P will disable all
remote fire signals.
3. DIS SNDRS/REM FIRE – Operation of I/P 1 will disable
all sounders and remote fire
signals.
4. DISABLE BUZZER – Operation of I/P 1 will disable
all remote fire signals.
This option allows the engineer to change the text that will be displayed
on the panel when Monitored I/P is activated. This is displayed in text
format and may be scrolled through by pressing the LEFT and RIGHT
keys. To change the text, highlight the character to be changed and
use the alphanumeric keypad to change that character. After changing
a character the cursor will automatically move to the next position. To
confirm the changes press ENTER.
This active control will allow the engineer to view or change the
operation of Monitored O/P 1. Use the UP AND DOWN arrow keys to
toggle through the following options. To confirm the changes press
ENTER.
1. REMOTE SOUNDER – Operation of O/P 1 will mimic that of a
conventional sounder circuit and will
de-activate on SILENCE.
2. REMOTE FIRE – Operation of O/P 1 will mimic that of a
remote fire circuit and will de-activate
on RESET.
3. OFF – O/P 1 will not be active.
This option allows the engineer to change the text that will be displayed
on the panel for Monitored O/P 1. This is displayed in text format and
may be scrolled through by pressing the LEFT and RIGHT keys. To
change the text, highlight the character to be changed and use the
alphanumeric keypad to change that character. After changing a
character the cursor will automatically move to the next position. To
confirm the changes press ENTER.