TWINFLEX
®
pro² Control Panel Engineering and Commissioning Manual
52
This active control will allow the engineer to view or change the
operation of the control event set for monitored input. Use the UP and
DOWN arrow keys to toggle through the following options. To confirm
the changes press ENTER.
1. SILENCE ALARMS Operation of I/P 1 will silence the
alarms.
2. RESET SYSTEM Operation of I/P 1 will reset the panel.
3. SOUND ALARMS Operation of I/P 1 will send the
evacuate signal to the panel.
4. SILENCE BUZZER Operation of I/P 1 will silence the
control panel buzzer.
This active control will allow the engineer to view or change the
operation of the remote fire event set for monitored input. Use the UP
and DOWN arrow keys to toggle through the following options. To
confirm the changes press ENTER.
1. REMOTE FIRE FULL Operation of I/P 1 will signal a
remote fire at the control
panel. All sounders and relays
will operate.
2. REMOTE FIRE NO RELAYS Operation of I/P 1 will signal a
remote fire at the control
panel and only the sounders
will operate.
This active control will allow the engineer to view or change the
operation of the technical event set for monitored input. Use the UP
and DOWN arrow keys to toggle through the following options. To
confirm the changes press ENTER.
1. LATCH Operation of I/P 1 will signal a
technical event at the control
panel. All outputs will trigger
and the panel will latch into
fire.
2. NON-LATCH Operation of I/P 1 will signal a
technical event at the control
panel. All outputs will trigger
for as long as the input is
activated.
10. Panel I/O
3. Monitored I/P
1. Input Type
1. Control Event
01/09/09 20:13 ENGR
1.SILENCE ALARMS
2.RESET SYSTEM
Press Enter Key
10. Panel I/O
3. Monitored I/P
1. Input Type
2. Remote Fire Event
01/09/09 20:13 ENGR
1.REMOTE FIRE- FULL
2.REM FIRE,NO RELAYS
Press Enter Key
10. Panel I/O
3. Monitored I/P
1. Input Type
3. Technical Event
01/09/09 20:13 ENGR
TECHNICAL EVENT
1.LATCH 2.NON-LATCH
Press Enter Key