TWINFLEX
®
pro² Control Panel Engineering and Commissioning Manual
51
This option allows the engineer to change the text that will be displayed
on the panel when Programmable I/P 2 is activated. This is displayed
in text format and may be scrolled through by pressing the LEFT and
RIGHT keys. To change the text, highlight the character to be changed
and use the alphanumeric keypad to change that character. After
changing a character the cursor will automatically move to the next
position. To confirm the changes press ENTER.
This active control will allow the engineer to view or change the
operation of monitored input. Use the UP and DOWN arrow keys to
toggle through the following options. To confirm the changes press
ENTER.
1. CONTROL EVENT – Operation of I/P 1 will operate a
control function on the panel.
2. REMOTE FIRE EVENT– Operation of I/P 1 will signal a remote
fire input at the control panel. Panel
outputs will be triggered and fire
indication will be shown at the control
panel.
3. TECHNICAL EVENT – Operation of I/P 1 will signal a
technical event at the control panel.
Panel outputs will be triggered but the
control panel will read technical alarm
and no fire indication will be given.
4. DISABLEMENTS – Operation of I/P 1 will activate a
disablement on the control panel.
5. DAY-NIGHT MODE – Operation of I/P 1 will activate the day
mode on the control panel
(TWINFLEX
®
Multipoint devices will
be disabled; TWINFLEX
®
ASD
devices will be disabled for smoke
only but not for heat).
6. PROGRAM I/P OFF – I/P 1 will not be active.