Emergency Command Center Manual — P/N LS10001-000FL-E:D 9/3/2014 87
Operation Operating Instructions
Play an inter-message tone (if programmed)
Play a primary evacuation tone only (if programmed)
Store the event in the history log
4.4.6 Manual Activation Restoral
Upon restoral the system will:
Turn the speaker zone LED(s) off
Turn the speaker circuit(s) off
Turn the audio amplifier(s) off
Turn the 24 VDC aux. power output off (if programmed)
Turn the speaker volume control override off
De-activate the “MNS active” output relay
De-activate the NAC output (if programmed to do so for mass notification)
Turn the “System in Use” LED off
4.4.7 Alarm/Alert Response, System Configured for Mass
Notification Only
Upon detection of an alarm/alert condition (any of CMD1 to CMD8 inputs active) the system will:
Turn all speaker zone LEDs on steady
Turn all speaker circuits on
Turn the appropriate audio amplifier(s) on
Turn the 24 VDC aux. power output on (if programmed)
Turn the speaker volume control override on
Turn the “System in Use” LED on steady
Activate the “MNS active” relay (if the system is programmed for mass notification)
Activate the NAC output (if programmed to do so for mass notification)
Play and repeat a leading tone (if programmed)
Play and repeat the appropriate audio message (if programmed to repeat)
Play an inter-message tone (if programmed)
Play a primary alert tone only (if programmed)
Store the event in the history log
4.4.8 Alarm/Alert Restoral, System Configured for Mass
Notification Only
Upon restoral the system will:
Turn the speaker zone LEDs off
Turn the speaker circuits off
Turn the audio amplifier(s) off
Turn the 24 VDC aux. power output off (if programmed)
Turn the speaker volume control override off
De-activate the “MNS active” output relay
De-activate the NAC output (if programmed to do so for mass notification)
Turn the “System in Use” LED off