71 Oil pressure Oil pressure is above upper limit
72 Cylinder head temperature Temperature of the diesel engine / Cylinder head is above upper limit
73 Winding temperature Winding temperature is above upper limit
74 Exhaust temperature Exhaust temperature is above upper limit
75 Electronics temperature Temperature of electronic system above upper limit
77 Starter motor output Current at output of starter motor is above upper limit
78 Glow plug circuit Current at output of the glow plugs is above upper limit
79 Flame-start system Current at output of flame-start system is above upper limit
80 Fuel supply Current at output of the fuel valve / fuel pump / DC generator exciter is above upper limit
81 Stop Solenoid hold Current at output of the hold coil of the stop solenoid is above upper limit
82 Stop Solenoid pull Current at output of the pull coil of the stop solenoid is above upper limit
83 Water pump/Fan Current at output of the water pump/fan is above upper limit
84 Current sensor supply Current at output of the current sensor is above upper limit
85 Boost relay Boost relay fault
86 Bus current Current at the CAN bus is above upper limit
89 Starter battery voltage Starter battery voltage is above upper limit
93 Power output relay Current at output of load-breaking relay is above upper limit
94 AC Voltage L2 AC Voltage L2 is above upper limit
95 AC Frequency L2 AC Frequency L2 is above upper limit
96 AC Current L2 AC Current L2 is above upper limit
97 AC Output L2 AC Output L2 is above upper limit
98 AC Voltage L3 AC Voltage L3 is above upper limit
99 AC Frequency L3 AC Frequency L3 is above upper limit
100 AC Current L3 AC Current L3 is above upper limit
101 AC Output L3 AC Output L3 is above upper limit
102 Inverter DC supply Current at output of the DC supply of the inverter is above the upper limit
103 Universal Output 1 (1A) Current at Universal Output 1 is above upper limit
104 Universal Output 2 (5A) Current at Universal Output 2 is above upper limit
105 AGT DC Voltage 1 Battery voltage too high
106 AGT DC Current 1 Battery current too high
107 AGT DC Voltage 2 Total voltage compared to battery voltage too high
108 AGT DC Current 2 Sum of battery and load current too high
109 AGT B6 Radiator Temperature at heat sink of the B6 bridge too high/Sensor error: Short circuit on temperature
sensor
110 AGT B6 Busbar (-) Temperature at busbar (-) of the B6 bridge too high/Sensor error: Short circuit on temperature
sensor
111 AGT B6 Busbar (+) Temperature at busbar (+) of the B6 bridge too high/Sensor error: Short circuit on temperature
sensor
126 Fuel temperature Fuel temperature too high/Sensor error Short circuit on temperature sensor
130 CAN communication interrupted The panel has lost contact with the control system
131 CAN communication interrupted The control system has lost contact with the panel
132 Service interval Service due
133 BUS Module lost (3ph measurement) Communication with the 3-ph Module interrupted
134 BUS Module lost (DC measurement) Communication with the AGT Module interrupted
135 Synchronisation error Problem with synchronisation of the output voltages of generators switched in parallel.
136 External motor controller
communication
Communication with the external motor controller (ECU) has been interrupted
137 Air filter Air filter has generated an error message
138 Diagnostic message (ECU) Control device of the diesel engine has transmitted a diagnostic warning
No. Description Basic