Panda fpControl
27.5.20 Chapter 2: Panda fpControl - Page 41
2.6.2.1 Table of Faults
See also the "Faults" chapter in the manual of the generator.
NoteThe relevant fault page of the
knowledgebase.fischerpanda.de can be called up via the
Internet.
(Internet connection required).
Fig. 2.6-1: Table of faults
No. Description Basic
1 AC Voltage L1 AC Voltage L1 is below its lower limit
2 AC Frequency L1 AC Frequency L1 is below its lower limit
5 Emergency-Off Emergency-off switch is active/has been pressed
7 Oil pressure Engine oil pressure is below its lower limit
8 Cylinder head temperature Cylinder head temperature sensor not available/Contact open/Cable break
9 Winding temperature Winding temperature sensor not available/Contact open/Cable break
10 Exhaust temperature Exhaust temperature sensor not available/Contact open/Cable break
11 Electronics temperature Temperature sensor for the electronic system (sensor on the fpControl circuit board) not
available/defective
13 Starter motor current Starter motor not connected/Starter motor defective
14 Glow plug circuit One or more glow plugs not connected or defective
16 Fuel supply Fuel valve/fuel pump not connected or defective
17 ETR Stop Solenoid hold Current at output of the ETR hold coil is below the lower limit
18 ETR Stop Solenoid pull Current at output of the ETR pull coil is below the lower limit
19 Water pump/Fan Fan/water pump not connected or defective
20 Current sensor Current sensor not available/Contact open/Cable break
21 Boost relay current Boost relay not connected or defective
25 Starter battery voltage Starter battery voltage too low
26 Engine speed error Engine speed (r.p.m.) too low
30 AC Voltage L2 AC Voltage L2 is below its lower limit
31 AC Frequency L2 AC Frequency L2 is below its lower limit
34 AC Voltage L3 AC Voltage L3 is below its lower limit
35 AC Frequency L3 AC Frequency L3 is below its lower limit
38 Inverter DC supply Current at output of the DC supply voltage of the inverter is below the lower limit
39 Universal output 1 (1A) Electrical load on Universal output 1 is defective/no consumer connected
40 Universal output 2 (5A) Electrical load on Universal output 2 is defective/no consumer connected
41 AGT DC voltage 1 Battery voltage too low
42 AGT DC current 1 Battery current too low
43 AGT DC voltage 2 Total voltage compared to battery voltage too low
44 AGT DC current 2 Sum of battery and load current too low
45 AGT B6 radiator Temperature sensor not available/Contact open/Cable break
46 AGT B6 busbar (-) Temperature sensor not available/Contact open/Cable break
47 AGT B6 busbar (+) Temperature sensor not available/Contact open/Cable break
62 Fuel temperature Temperature sensor not available/Contact open/Cable break
63 Fuel level The fuel level has reached its lower limit
65 AC Voltage L1 AC Voltage L1 is above upper limit
66 AC Frequency L1 AC Frequency L1 is above upper limit
67 AC Current L1 AC Current L1 is above upper limit
68 AC Output L1 AC Output L1 is above upper limit
70 Servomotor current Servomotor current is above upper limit