EasyManua.ls Logo

Fisher FIELDVUE DLC3010 - Page 100

Fisher FIELDVUE DLC3010
116 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Instruction Manual
D102748X012
Field Communicator Menu Tree
October 2014
100
Table
B‐1.
Fast
Key
Sequence
Function Fast-Key Sequence See Figure
Active Alerts 3-1 B‐8
Alarm Jumper 1-7-3-1-1 B‐2
Analog Output
1-5 B‐2
3-2-3 B‐8
Burst Mode 2-4-1 B‐6
Burst Options 2-4-2 B‐6
Calibration, Full 2-5-1-2 B‐7
Calibration, Partial 2-5-1-3 B‐7
Calibration, Temperature 2-5-2-1 B‐7
Change Process Temperature
2-2-3-2
(1)
B‐4
2-2-3-2-2
(2)
B‐4
Change Primary Variable 2-2-2-1-2 B‐1
Change Torque Rate 2-2-1-3-2 B‐4
Comm Status 1-2 B‐2
Date
1-7-1-8 B‐2
2-2-4-2 B‐4
DD Information 1-7-2-5 B‐2
Decimal Places 2-2-5-4 B‐4
Descriptor
1-7-1-9 B‐2
2-2-4-3 B‐4
Device ID 1-7-1-4 B‐2
Device Status 1-1 B‐2
Displacer Units 2-2-1-2 B‐4
Display Alert/Saturation Level 1-7-3-1-2 B‐2
Display Mode 2-2-5-2 B‐4
Distributor 1-7-1-2 B‐2
Enter Constant Density 2-2-3-1-3
(2)
B‐1
Field Device Revision 1-7-2-2 B‐2
Final Assembly Number
1-7-1-7 B‐2
2-2-4-8-3 B‐4
Firmware Revision 1-7-2-3 B‐2
Guided Setup 2-1 B‐3
Hardware Revision 1-7-2-4 B‐2
HART Tag
1-7-1-1 B‐2
2-2-4-1 B‐4
HART Universal Revision 1-7-2-1 B‐2
Instrument Mounting 2-2-1-4 B‐4
Instrument Serial Number
1-7-1-5 B‐2
2-2-4-8-1 B‐4
Instrument Temperature 3-2-4 B‐8
Instrument Temperature Alerts 2-3-2-1 B‐5
LCD Configuration 2-2-5-1 B‐4
LCD Test 3-3-1-1
(3)
B‐8
Level Offset 2-2-2-1-4 B‐4
Loop Test
3-3-1-1 B‐8
3-3-1-2
(3)
B‐8
Lower Density Table
2-2-3-1-1-1
(4)
B‐4
2-2-3-1-1-2
(5)
B‐4
Lower Fluid Density
2-2-3-1-1 or 3-2-7
(4)
B‐4
2-2-3-1-2 or 3-2-8
(5)
B‐4
Lower Range Value
2-2-2-3-2 B‐4
2-3-1-4 B‐5
Function Fast-Key Sequence See Figure
Lower Sensor Limit 2-2-2-2-2 B‐4
Measure Density 2-2-3-1-4
(4)
B‐4
Message 2-2-4-4 B‐4
Minimum Sensor Span 2-2-2-2-3 B‐4
Model 1-7-1-3 B‐2
Number of Request Preambles 2-2-4-7 B‐4
Percent Range
1-4-2 B‐2
3-2-2-2 B‐8
Physical Signalling Code 2-2-4-6 B‐4
Polling Address 2-2-4-5 B‐4
Primary Variable Hi Alerts 2-3-1-1 B‐5
Primary Variable Lo Alerts 2-3-1-2 B‐5
Process Temperature
1-6-2 B‐2
2-2-3-2-3
(2)
B‐4
2-2-3-3
(1)
B‐4
3-2-5-2 B‐8
Process Temperature Alerts 2-3-2-2 B‐5
Process Temperature Source
1-6-1 B‐4
2-2-3-2-1
(2)
B‐4
2-2-3-
(1)
B‐2
3-2-5-1 B‐8
PV Alerts Threshold Deadband 2-3-1-5 B‐5
PV is
1-3 B‐2
2-2-2-1-1 B‐4
PV Units 2-2-2-1-3 B‐4
PV Value
1-4-1 B‐2
3-2-2-1 B‐8
Reset Device 3-3-2-2 B‐8
Restore Factory Defaults 3-3-2-1 B‐8
RTD Wire Resistance
2-2-3-2-4
(2)
B‐4
2-2-3-4
(1)
B‐4
Scaled D/A Trim 2-5-2-2-1 B‐7
Sensor Damping 2-2-1-5 B‐4
Sensor Serial Number
1-7-1-6 B‐2
2-2-4-8-2 B‐4
Sensor Unit 2-2-1-1 B‐4
Set Level Offset 2-2-2-1-5 B‐4
Torque Rate
2-2-1-3-1 B‐4
3-2-6 B‐8
Torque Tube Compensation
Selection
2-2-1-3-4 B‐4
Torque Tube Compensation Table 2-2-1-3-5 B‐4
Torque Tube Material 2-2-1-3-3 B‐4
Upper Density Table 2-2-3-1-1-1
(4)
B‐4
Upper Fluid Density
2-2-3-1-1
(4)
B‐4
3-2-7
(4)
B‐8
Upper Range Value
2-2-2-3-1 B‐4
2-3-1-3 B‐5
Upper Sensor Limit 2-2-2-2-1 B‐4
Write Lock 1-7-3-2-1 B‐1
Write Lock Setup 1-7-3-2-2 B‐1
1. If PV is Density
2. If PV is Level or Interface.
3. LCD Configuration is installed
4. If PV is Level
5. If PV is Interface

Table of Contents

Other manuals for Fisher FIELDVUE DLC3010

Related product manuals