Instruction Manual
D103176X012
Detailed Setup and Calibration
June 2017
11
Table 2‐1. Factory Default Detailed Setup Parameters
Setup Parameter Default Setting
(1)
Control Mode
Restart Control Mode
Burst Mode Enabled
Burst Mode Command
HART Tag
Analog
Resume Last
No
3
As specified on order
Message
Description
Date
Valve Serial Number
Polling Address
Blank
Blank
Factory Calibration Date
Blank
0
Max Supply Pressure
Zero Control Signal
100
(2)
Open
(2)
Analog Input Units
Analog In Range High
Analog In Range Low
Travel Range High
Travel Range Low
mA
20 mA
4.0 mA
100%
0%
Pressure Units
Temperature Units
Input Characteristic
Setpoint Filter Time
PSI
(2)
F
Linear
Filter Off
Travel Limit High
Travel Limit Low
Travel Cutoff High
Travel Cutoff Low
125%
-25%
99.5%
0.5%
Minimum Opening Time
Minimum Closing Time
Integral Gain
Integral Deadband
Travel Hi/Lo Alert Enabled
Travel Hi Hi/Lo Lo Alert Enabled
0 secs
0 secs
1 repeat/minute
0.5%
No
No
Travel Alert High Point
Travel Alert Low Point
Travel Alert High-High Point
Travel Alert Low-Low Point
Travel Alert Deadband
125%
-25%
125%
-25%
1%
Travel Deviation Alert Enable
Travel Deviation Alert Point
Travel Deviation Time
Yes
7%
5 secs
Cycle Counter Alert Enable
Cycle Counter Alert Point
Cycle Counter Deadband
Cycle Counter
No
2,147,483,646
3%
0
Travel Accumulator Alert Enable
Travel Accumulator Alert Point
Travel Accumulator Deadband
Travel Accumulator
No
2,147,483,646%
3%
0
Drive Alert Enable
Flash ROM Fail
Ref Voltage Fail
No
No
No
Drive Current Fail
Critical NVM Fail
Temperature Sensor Fail
Pressure Sensor Fail
Travel Sensor Fail
No
No
No
No
No
1. The settings listed are for standard factory configuration. DVC2000 instruments can also be ordered with custom configuration
settings. For the default custom settings, refer to the order requisition.
2. If the instrument is shipped mounted on an actuator, these values depend upon the actuator on which the instrument is mounted.

Table of Contents

Other manuals for Fisher FIELDVUE DVC2000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fisher FIELDVUE DVC2000 and is the answer not in the manual?

Fisher FIELDVUE DVC2000 Specifications

General IconGeneral
BrandFisher
ModelFIELDVUE DVC2000
CategoryController
LanguageEnglish

Related product manuals