EasyManua.ls Logo

FläktGroup Multi-DENCO - Page 110

FläktGroup Multi-DENCO
144 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning Multi-DENCO
110 FläktGroup DC-2013-0101-GB • Subject to modifications • R5-08/2020
8.3.11 Systems fitted with a Pressure Relief Valve (PRV)
Pressure Relief Valves could be fitted:
On W-Version units on the liquid receivers in the WaterCool Module
On P-Version units on the shell and tube condenser in the WaterCool Module
On outdoor units (condensers) that are fitted with liquid receivers or winter kits
(A-Version)
8.3.12 Variances for winter kit
Units operating in low ambient temperatures may be fitted with a winter kit. The system
operates as a 'liquid backup'. At high ambient temperatures, the system regulates so
that liquid refrigerant is stored in the liquid receiver. At low ambient temperatures liquid
refrigerant is stored/backed-up in the condenser coil instead.
The components of the winter kit are:
Electronic Regulation Valves (ERV)
Condenser fans
Liquid receiver with trace heating
Control circuit transformer for controlling the ERVs (Evolution Driver)
Control panel heater
Mains Circuit Breaker (MCB) in the indoor units electrical panel (power supply to the
winter kit)
Commissioning engineers must observe the good practices with the following addi-
tional requirements for winter kits.
Procedure
1. Calculate the 'system refrigerant'.
This is the refrigerant required to charge a standard system without a winter kit
option (indoor/outdoor unit and interconnecting pipework).
2. Calculate the refrigerant required to fill the liquid receiver to 80% (see Tab. 8-4).
Pressure Relief Valves (PRV) are essential safety devices to prevent the risk of
excess pressure within the direct expansion circuit / liquid receiver causing an
explosion or rupture.
During pressure testing, PRVs are isolated using in-line shut off valves (SOV) to
prevent any relief whilst operating in a control environment.
If the SOV(s) are not set to the “Open” position AFTER testing, there is a HIGH
RISK of explosion if excessive pressures are created within the direct expansion
circuit.
At any time, outside of pressure testing:
Ensure all SOVs that isolate PRVs are in the OPEN position
NOTICE
Overfilling of liquid receivers can result in poor system performance or failure.
The liquid receiver should never exceed 80% full.

Table of Contents

Related product manuals