Why does my FläktGroup Air Conditioner have high pressure in the refrigeration system?
- DdarinbensonAug 2, 2025
If the FläktGroup Air Conditioner's refrigeration system has high pressure, it could be due to several reasons. First, there might be too much refrigerant in the system; compare current conditions with the commissioning report and re-commission the unit if there are significant changes. Another cause could be that the outdoor fans aren't working, so check the ‘Fault’. Also, inspect the unit for damage to any fuse or relay that is part of the refrigeration circuit operation. Finally, the outdoor heat exchanger might be blocked or dirty; clean the heat exchanger fins and clear any debris around the unit.