EasyManua.ls Logo

FläktGroup Multi-DENCO - Product Series Overview

FläktGroup Multi-DENCO
144 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Multi-DENCO Overview of Units and Scope of Supply
FläktGroup DC-2013-0101-GB • Subject to modifications • R5-08/2020 9
1.3 Product series overview
There are 6 versions of the Multi-DENCO product: A-Version, C-Version, X-Version,
F-Version, W-Version and P-Version.
Fig. 1-1: A Multi-DENCO Unit
Common features &
options
– 7 standard box sizes (010, 018, 030, 045, 065, 092 and 130)
– Cooling capacities up to 150 kW
– Available with both upflow or downflow air paths
– Large EC plug fans
– Integrated and/or remote temperature and humidity sensors
– Large surface area for heat exchanger coil
– Available with full height panel doors or with door mounted grilles
– Humidification and heating options available
– Standard control software and hardware that is compatible for all versions
– Building Management System (BMS) interface compatible
A-Version – Refrigeration based cooling
– R410A used as standard
– Inverter compressors as standard (fitted in indoor unit)
– Electronic expansion valve as standard (fitted in indoor unit)
– Typically supplied with an outdoor condenser
C-Version – Chilled water based cooling
– Can operate with Glycol
– A method of heat rejection separate to Multi-DENCO unit (e.g. Chiller)
– Can be provided with 3-way, 2-way or 2-way PICV valves and a variety of actuators
X-Version – Refrigeration based cooling
– R410A used as standard
– Available for sizes 010 to 045
– Inverter compressors as standard (fitted in outdoor unit)
– Electronic expansion valve as standard (fitted in outdoor unit)
– Typically supplied with an outdoor condensing unit
F-Version – Two circuits within 1 unit: one FreeCool circuit and one direct expansion circuit.
– Available for sizes 030 to 065
– Energy saving Free-Cooling with additional / backup refrigerant circuit
– R410A used as standard
– Inverter compressors fitted as standard (fitted in indoor unit)
– Electronic expansion valve fitted as standard (fitted in indoor unit)
– EC water pump as standard (fitted in indoor unit).
– (Optional) Hybrid outdoor unit combining condenser and drycooler

Table of Contents