EasyManua.ls Logo

FläktGroup Multi-DENCO - Unit Placement and Handling

FläktGroup Multi-DENCO
144 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation Multi-DENCO
40 FläktGroup DC-2013-0101-GB • Subject to modifications • R5-08/2020
5.3 Unit placement
Generally, it is easier to install the base stand before the raised floor is completed. The
unit can then be positioned after the floor. Reuse transport packing to provide protec-
tion whilst positioning.
Fig. 5-8: Heavy-duty jack
Multi-DENCO units are heavy and can have a high centre of gravity. Failure to
safely secure the equipment may result in death or serious injury.
Never stand beneath suspended loads.
Multi-DENCO units are heavy and can have a high centre of gravity. The unit, or
parts of the unit can, tip and fall. Failure to safely install the equipment may result
in death or serious injury.
Secure the unit against tipping before removing the unit from the pallet.
Do not lean against or lean objects against the unit.
Do not expose any part of your body, limbs or hands to the space between the
unit and any substructures (see chapter 5.2) or between the unit and the ground.
NOTICE
During installation and placement, weight loads may be increased or concen-
trated. Failure to account for this can cause damage to the floor or the unit.
Ensure the floor can withstand the weight and forces of the unit, lifting equipment
and operators.
For installation on a raised floor, ensure flooring can support increased point
loads.
NOTE!
We recommend using two heavy-duty jacks. Always refer to the manu-
facturer's instructions when operating the heavy-duty jacks. For further
advice, consult your local sales office.

Table of Contents