EasyManua.ls Logo

FOR-A MFR-3100EX - Switches on the Card

FOR-A MFR-3100EX
86 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
31
2-5-4. Switches on the Card
IMPORTANT
Do not access internal cards or make connections with the unit powered ON. Always power
OFF all connected units / disconnect power cords prior to accessing the interior.
Further note that adjustments and maintenance should only be performed by qualified
technical personnel familiar with FOR-A equipment.
Remove the two screws on both sides of the MFR-GPI to access the internal card as shown
below. The figure below shows the factory default switch settings.
Switch
Function / Settings
S2, S3
Used for maintenance. Do not use.
S4
Used for maintenance. Do not use. (The
factory default setting is as shown at right.
The black boxes () represent switches.)
S5, S6,
S7,
S8, S9,
S10
Used for maintenance. Do not use.
S11
Used for maintenance. Do not use.
S12, S14
Used to select RS-232C/RS-422 for SERIAL
1.
The default setting is RS-232C (both
switches to the left). To change to RS-422,
set both switches to the right.
Switch
Settings
RS-
232C
(Factory
default
setting)
S13, S15
Used to select RS-232C/RS-422 for SERIAL
2.
The default setting is RS-232C (both
switches to the left). To change to RS-422,
set both switches to the right.
S16, S18
Used to select RS-232C/RS-422 for SERIAL
3.
The default setting is RS-232C (both
switches to the left). To change to RS-422,
set both switches to the right.
RS-422
S17, S19
Used to select RS-232C/RS-422 for SERIAL
4.
The default setting is RS-232C (both
switches to the left). To change to RS-422,
set both switches to the right.
Front
OFF
ON
OFF
ON

Table of Contents