2.7 Emergency procedure
2.7.1 System overheating
If the system overheats and the safety devices fail to operate, proceed
as follows:
Keep all the doors on the boiler closed.
Turn off the boiler with the key
Under no circumstances use the main switch!
Open all mixer taps, switch on all pumps.
Fröling heating circuit control takes over this function in
automatic operation.
Leave the boiler room and close the door.
Open any available radiator thermostat valves
If the temperature does not drop, inform the installer or Fröling
customer services:
Page 77, 8.2 Manufacturer address
2.7.2 Smell of flue gas
Smell of flue gas!
Flue gases can cause fatal poisoning!
Keep all the doors on the boiler closed.
Turn off the boiler with the key
Under no circumstances use the main switch!
Air the room where the boiler is installed
Close the fire protection door and doors to living areas.
2.7.3 Fire
Fire!
In case of fire, there is risk of burns and explosions!
Turn off the boiler
Use a tested fire extinguisher for fire class AB to fight the fire
AB powder