Lambdatronic P 3100 control system
Menus and parameters
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Page 29
Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
B0190806
Setting heating times
Heating times ... Heating prog. 1 ... Heating phase 1 start 06:00
Heating phase 1 end 11:00
Heating phase 2 start 15:00
Heating phase 2 end 23:00
Lowered outside the
specified heating times.
Heating prog. 2
:
:
:
Heating prog. 14...
2 heating phases each, like heating prog. 1.
You can program up to 14 heating times each with two
heating phases.
These heating times can be allocated to the individual
days of the week under the parameter “Weekly program”
for the heating circuits 1-4.
Allocating heating times to heating circuits
Heating circuit 1 ...
Weekly program
Mo Tu We Th Fr Sa Su
1 1 3 1 1 2 5
Allocating heating times 1- 14 to
the individual days of the week
for heating circuit 1
Heating curve ... Flow temp. at
external -10°C 60°C
Flow temp. at
external +10°C 40°C
These two parameters are the
work points for adjusting the
heating curve to the relevant
system
Room temp.
set value 21°C
Desired room temperature
during heating (only with
remote control).
Room temp. set
value Drawdown
mode 16°C
Desired room temperature
during drawdown mode (only
with remote control).
Ex.temp.
heating limit 18°C
If the external temperature
exceeds this value during the
heating phase, the heating
circuit pump and mixer are
switched off.
Outside temp
Heating limit
Drawdown
mode 7°C
If the external temperature
exceeds this value during
drawdown mode, the heating
circuit pump and mixer are
switched off.
Heating circuit 2 ...
Heating circuit 3 ...
Heating circuit 4 ...
Settings as with heating circuit 1
Flow temperature
External temperature
Example of floor
heating
Example of
radiators