Installers and service technicians
Parameter list - Lambdatronic P 3100
Page 76
B0190806
s
7
7.5.6 Manual anal. menu OUT
Used to test the digital outputs and is intended only for heating
engineers. The display depends on the configuration.
ID fan A 0%
Storage tank LP
A 0%
Storage tank loading pump
DHW LP A 0%
DHW tank loading pump
Pump 1 A 0%
Pump 2 A 0%
Pump 3 A 0%
Comb air fan
A 0%
Supply air fan
Stoker A 0%
Function check is also possible in “Manual control” menu
Discharge
screw A 0%
Function check is also possible in “Manual control” menu
HCP 1 A 0%
Collector pump for solar systems (if available)
A 0%... Automatic, OFF
A 1%-100%... Automatic, corresponding value ON
A... AUTOMATIC
0%... Manual OFF
1%-100%... Manual with corresponding value ON
7.5.7 Manual digi.menu IN
Used to test the digital inputs and is intended only for heating
engineers. The display depends on the configuration.
Door sensor A 0
Limit thermostat
emergency off A 1
Safety temperature limiter / EMERGENCY STOP
Jam sensor A 0
“Jam sensor” for suction feed “Gravity shaft level sensor”
for screw discharge
Level MIN A 0
Input not covered
Level MAX A 1
Only for suction feed: Maximum for day store ends suction
cycles.
Com.Ch. exc.
press. A 1
Combustion chamber excess pressure monitor: “Opener”
Ext. req. A 0
For external heat requirements, e.g. from a house control
system input “S6 boiler release” in pellet module
A 0… Automatic, OFF A… AUTOMATIC
A 1... Automatic, ON 0... Manual OFF
1… Manual ON