Troubleshooting
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria Page 43
Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
B0190806
6
Error text Code
Type
Cause of error Error correction
Store temp. up. false 008 W Sensor signal damaged Check sensor and sensor cable
Store temp. mid. false 010 W Sensor signal damaged Check sensor and sensor cable
Outfeed system error
(with screw discharge unit)
027 S Gravity shaft level sensor
does not recognise any
material for 60 minutes:
No pellets in trough
Bridge formation over
trough
Sensor incorrectly set
Discharge screw drive is
not working
Refill pellets in store
ATTENTION! Do not feed any
pellets into the pellet burner
manually - danger of flash fires!
Break up blocks of fuel, check
length of pellets
Readjust the sensor
Check drive
Check/clean outfeed
system (for screw suction
systems)
For information on errors in
manual universal suction
systems see the next page!
021 S For screw suction
systems:
The MAX sensor is not
reached after 45 minutes of
suction:
No pellets in trough
Bridge formation over
trough
Hose or hose connections
blocked
Sensor incorrectly set
Screw drive not working
Jam sensor is covered for
longer than 5 minutes:
Suction point is blocked
Refill pellets in store
ATTENTION! Do not feed any
pellets into the pellet burner
manually - danger of flash fires!
Break up blocks of fuel, check
length of pellets
Remove blockage, shake hose
Readjust the sensor
Check drive
Clear blockage and remove
foreign bodies if necessary,
check pellet length