Changing TAG
Writing the com-
mand
1
E258 - Set TAG write command to 0
2
E265-280 - Set TAG address to 0xE001 (gas pre-flow)
- Low byte 0x11
- High byte 0xE0
3
E281-296 - Set TAG address to 0x0898 - 2200 dec. (gas post-flow - 2.2 seconds)
- Low byte 0x98
- High byte 0x08
4
E258 - Set TAG write command to 1
Reading the com-
mand
1
E257 - Set TAG read command to 0
2
E265-280 - Set TAG address to 0xE001 (gas post-flow)
- Low byte 0x11
- High byte 0xE0
3
E257 - Set TAG read command to 1
4
Data from A281-296 - read TAG value - 2200 dec. (gas post-flow - 2.2 seconds)
- Low byte 0x98
- High byte 0x08