4
Strip the insulation of the single con-
ductors by 12 mm.
Select the cable cross section in ac-
cordance with the instructions in Per-
missible cables for the electrical con-
nection from page 67.
Lift to open the terminal's operating
lever and insert the stripped single
conductor into the slot provided as far
as it will go.
Then close the operating lever until it
engages.
IMPORTANT!
Only one line may be connected to
each pole. The AC cables can be con-
nected to the AC terminal without fer-
rules.
5
L1 Phase conductor
N Neutral conductor
PE Ground conductor
6
Insert the AC terminal into the AC slot
until it engages. Fasten the union nut
of the cable gland with a torque of
6 7 Nm.