50
(26) Cell fault detected
(27) Battery not supported
(28) Battery heavily discharged - safety charging is being carried out
(29) Battery is connected with reverse polarity
(30) Thermal runaway
(100) - (400) General battery fault
Status codes in the event of a CAN fault
No. Cause
(51) Battery not responding
(52) Battery data cannot be requested
(53) Battery voltage not supported
(54) Communication fault
(55) Battery fault
(56) Battery does not switch on
(57) Message time limit exceeded
(58) Registration failed
Status codes in the event of a charging error
No. Cause
(31) Timeout in I1 phase
(32) Timeout in U1 phase
(33) Battery overvoltage in the I2 phase
(34) Ah limit exceed
(35) Timeout in I2 phase
(36) Target voltage in I2 phase not reached (with format characteristic only)
(37) Problem with RI charge
(38) Set charging time cannot be reached
(39) Timeout in RI charge
Status codes in the event of a fault in the primary circuit
No. Cause
(500) Module 1 (top) temperature sensor faulty

Table of Contents

Other manuals for Fronius Selectiva Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fronius Selectiva Series and is the answer not in the manual?

Fronius Selectiva Series Specifications

General IconGeneral
Device CategoryBattery Charger
ManufacturerFronius
SeriesSelectiva
Microprocessor ControlledYes
Battery TypesLead-acid, AGM, Gel
Protection ClassIP20
Protection FeaturesReverse polarity, short circuit, overvoltage, overtemperature
DimensionsVaries by model
WeightVaries by model
Output Voltage12/24 V DC