Programming instructions
4.12 QS4 Technical Reference Manual
Table 4-4: AutoLoop initial settings for SIGA devices
SIGA Device Personality Description Device Type Edit?
SIGA–IPHS, –PHS,
–PS, –IS
none Smoke detector settings as follows:
Sensitivity: Least
Verification: None
Prealarm: None
Alarm FPP/CU
SIGA–HFS, HRS,
–IM
none Heat detector settings not programmable Alarm FPP/CU
Single-stage pull
stations
01 Class B Alarm Latching Pull FPP/CU
Dual-stage pull
stations
01 Class B Alarm Latching Monitor FPP/CU
01 Class B Alarm Latching Pull FPP/CU
SIGA–APS 03 Class B Active Non-Latching Monitor FPP/CU
03 Class B Active Non-Latching Monitor FPP/CU
SIGA–(M)CC1(S) 05 Riser selector Common Alarm
Output
FPP/CU
SIGA–(M)CC2 07 Dual riser selector Common Alarm
Output
FPP/CU
SIGA–(M)CR(R) 08 Dry contact Nonsupervised
Output
FPP/CU
SIGA–(M)CT1 01 Class B Alarm Latching Alarm FPP/CU
SIGA–(M)CT2 01 Class B Alarm Latching Alarm FPP/CU
01 Class B Alarm Latching Alarm FPP/CU
SIGA–DTS 01 Class B Alarm Latching Alarm FPP/CU
SIGA–IO 31 Monitor Input/Output N.O. Monitor FPP/CU
SIGA–MAB 00 Class A Signal Output Monitor FPP/CU
00 not used
SIGA–UM 00 Class A Signal Output Monitor FPP/CU
00 not used
SIGA–MM1 03 Class B Active Non-Latching Monitor FPP/CU
SIGA–WTM 02 Class B Active Latching - Delayed Alarm FPP/CU
04 Class B Active Latching. Supervisory FPP/CU
SIGA–(M)RM1 23 Riser monitor - 24 Vdc Monitor FPP/CU
Note: If you use Signature devices from another system, the AutoLoop utility uses the attributes programmed from
the previous system as the initial settings for a general alarm system.