Operating instructions
QS4 Technical Reference Manual 3.7
Instructions for the Level 3 operator (maintenance mode access)
Tasks that require you to log on as a Level 3 operator
What is it you want to do This is how you do it
Log onto the panel as a Level 3
operator
1. Press Menu.
2. Choose Login then enter the password required for Level 3
access.
Change the password required for
Level 2 access
1. From the Main Menu, select Program.
2. Select Edit Password.
3. Select Level 2 then enter the new password.
Get a list of all the hardware and
software components installed on a
panel and their revision levels
1. Press Menu.
2. Choose Reports > Revision.
3. Enter the panel number.
4. Choose Display to view the list on the CPU/Display unit.
— or —
Choose Printer to print the list.
Set the system time and date
1. Press Menu.
2. Choose Program > Time/Date.
3. Choose Enter Time, then press DEL until the display shows
HHMMSS.
Enter the time in 24–hour format where HH is the hour, MM
is the minutes, and SS is the seconds.
Example: To set the time for 1:00 p.m., enter 130000.
4. Select Enter Date.
Enter the date where MM is the number of the month, DD is
the date, and YYYY is the year.
Example: To set the date for January 1, 2001, enter
01012001.