Programming instructions
QS4 Technical Reference Manual 4.15
What is it you want to do This is how you do it
Change the performance class of the Signature
loop wiring
AutoLearn default: Wiring is Class B.
1. On the Configure menu, choose Cards > Edit
then enter the card address number.
2. Choose Config Card.
3. Choose Wiring Class then choose how the loop
is wired to the SLIC.
4. Choose Exit > Save Edits, then wait while the
database is updated.
Enter location message text for an automatic
detector
1. On the Configure menu, choose Cards > Edit
and then enter the card address number of the
loop controller.
2. Choose Config Detect > Edit > Enter Serial #
and then scan or enter the detector's serial
number.
3. Choose Message then scan in the text that you
want sent when the detector signals an event.
4. Choose Exit > Save Edits.
Change the Alarm Sensitivity setting of a
smoke detector
WARNING: Selection of the appropriate detector
technology and sensitivity settings should result
from a careful analysis of the hazard,
environmental conditions, and expected results.
1. On the Configure menu, choose Cards > Edit
and then enter the card address number of the
loop controller.
2. Choose Config Detect > Edit > Enter Serial #
and then scan or enter the detector's serial
number.
3. Choose Sensitivity then choose the alarm
sensitivity setting you want the detector to use.
Refer to Table 4-5 and Table 4-6.
4. Choose Exit > Save Edits.