Programming instructions
4.20 QS4 Technical Reference Manual
Table 4-7: Device type descriptions
Alarm Device type assigned to IDC circuits that connect to automatic or a combination of automatic
and manual alarm-signal initiating devices. Alarm circuits signal Alarm Active events.
Alarm Output Device type assigned to IDC/NAC circuits that connect to notification appliances that you want
turned on automatically when the panel processes an alarm signal. Alarm Output circuits turn
off when you press Alarm Silence and turn on when you press Drill.
Audible
Device type assigned to IDC/NAC circuits that connect to audible notification appliances
(horns). Audible circuits turn off when you press Alarm Silence and turn on when you press
Drill.
Heat Device type assigned to IDC circuits that connect to automatic alarm-signal initiating devices
that detect a rise in the surrounding temperature. Heat circuits signal Heat Alarm events.
Monitor Device type assigned to IDC circuits that connect to monitor-signal initiating devices that
monitor the operation of ancillary system functions. Monitor circuits signal Monitor events.
Output Device type assigned to IDC/NAC circuits that supervise their output wiring for opens and
shorts. Output circuits do not turn off when you press Alarm Silence or turn on when you press
Drill.
Pull Device type assigned to IDC circuits that connect to manually operated alarm-signal initiating
devices. Pull circuits signal Pull Station events.
Supervisory
Device type assigned to IDC circuits that connect to supervisory-signal initiating devices that
detect abnormal conditions that could make the sprinkler system inoperative or ineffective.
Supervisory circuits signal Supervisory events.
Tamper Device type assigned to IDC circuits that connect to supervisory-signal initiating devices that
detect when someone tampers with a component of the sprinkler system. Tamper circuits signal
Tamper events.
Verified Smoke Device type assigned to IDC circuits that connect to automatic alarm-signal initiating devices
that use alarm verification. Verified Smoke circuits signal Alarm Verify events when the fire
condition is first detected then Alarm Active events after verifying the fire condition exists.
Visible
Device type assigned to IDC/NAC circuits that connect to visual notification appliances
(strobes). Visible circuits do not turn off when you press Alarm Silence or turn on when you
press Drill unless programmed to do so.
Water Flow
Device type assigned to IDC circuits that connect to alarm-signal initiating devices that detect
water flowing through the sprinkler system. Water Flow circuits signal Waterflow events.