Advent Commercial Fire System
Control Units for Fire Protective Signaling Devices (UL
864)
Basic system using:
Commercial Fire (60-562-03 or 60-562-06) Control Panel
24 VAC output, 100 VA Class I, 110 VAC, 60 Hz (60-830)
Line Carrier AC Power Transformer
plus:
SuperBus 2000 Fire Alphanumeric Touchpad (60-810-04)
SuperBus 2000 Dual Phone Line Module (60-768)
UL 864 listed 4-8 ohm, 15W Speaker
Hardwire 2-Wire Smoke Detector (Compatibility Identifier
#60-562, 20 per loop maximum.):
System Sensor models 2100S, 2100TS, 2100D, 2100TD, 2400,
or 2400T added (learned) into
Zone Type 80
Sentrol models 429AT, 521B, or 521BXT added (learned) into
Zone Type 80
The basic system may also include:
SuperBus 2000 Commercial RF Transceiver (60-856-95)
for use with listed wireless signaling devices
Wireless Smoke Sensor (60-849-01-95) added (learned)
into Zone Type 80
SuperBus 2000 Printer Automation Module (60-854) for
use with a listed printer
AL602 ITI NAC Power Supply (13-522)
24V Smoke Loop SnapCard (60-767)
Universal Fire Transmitter (UFT) (60-917-95)
Zone Types 11 (Extended Entry/Exit Delay), 12 (Twice
Extended Delay), 15 (Instant Interior), 17 (Instant Interior),
18 Instant Interior), 19 (Delayed Interior), 20 (Delayed Inte-
rior), 24 (Local Instant Auxiliary), and 25 (Local Special
Chime) are not to be used as primary protection circuits in
UL 864 listed systems and are for supplementary use only.
Zone Types 27, 28, and 32 (Custom Outputs) may not be
used in UL 864 listed systems.
xx102 One-Time Reset Enabled 0-Off
17034 Phone Test Interval 1 Day
17036 AC Stable Time 90 sec. maximum
17041 Hours to Delay Before
Reporting AC Failure
8 hours (or less)
17049 RF Supervisory Time A 4 hours
17069 No Phone Line Attached 0-Off
17072 Enable RF Jam Detect 1-On
17073 Battery Test Interval 1=4 hours
17076 Commercial or Residential
Installation
1-Commercial
17078 Detect Receiver Failure 1-On
17079 Alarm Messages Played at
High Volume
1-On (High)
17096 Report System Events 1-On
47004 Zone Attributes (edit zones) N/A
xx = Two digit partition number.
yy = Two digit non-pager phone number.
Table 3. UL 864 Listed System Settings
Feature
No.
Feature Required Setting
xx002 Siren Time Out 6 min. minimum
yy004 Comm Format 0 Contact ID
xx081 Disable Siren 1-On
xx083 Tamper Signals from Fire
Zones are Alarms
0-off
xx085 Enable Police Panic Keys 1-On
xx086 Enable Auxiliary/Medical
Panic Keys
1-On
Table 2. UL 609 Listed System Settings (Continued)
Feature
No.
Feature Required Setting
xx087 Enable Fire Panic Keys 0-Off
xx088 Report Partition/Area Events
to Central Station
1-On
xx091 Print Partition/Area Events 1-On
xx092 Enable Auto Force Arming 0-Off
xx097 Exterior Arming Verification 0-Off
xx102 One-Time Reset Enabled 0-Off
17034 Phone Test Interval 1 Day
17036 AC Stable Time 90 sec. maximum
17041 Hours to Delay Before
Reporting AC Failure
8 hours (or less)
17049 RF Supervisory Time A 4 hours
17069 No Phone Line Attached 0-Off
17072 Enable RF Jam Detect 1-On
17073 Battery Test Interval 1-4 hours
17076 Commercial or Residential
Installation
1-Commercial
17078 Detect Receiver Failure 1-On
17079 Alarm Messages Played at
High Volume
1-On (High)
17084 First Disarm Silences Fire
Alarmd and Second Disarm
Cancels the Alarm
1-On
17096 Report System Events 1-On
17099 Print System Events 1-On
17111 Time Fire Alarm is Silenced 30 sec. (or less)
17126 Unsilence Alarm after
Silencing Period
1-On
47004 Zone Attributes (edit zones) N/A
xx = Two digit partition number.
yy = Two digit non-pager phone number.
Table 3. UL 864 Listed System Settings (Continued)
Feature
No.
Feature Required Setting