3
Advent Commercial Fire System
Household Fire Warning System Units (UL 985)
Basic system, plus:
Hardwire Smoke Detector (Compatibility Identifier
60-562, 20 per loop maximum):
System Sensor models 2100S, 2100TS, 2100D,
2100TD, 2400, or 2400TH added (learned) into Zone
Type 80.
Sentrol models 429AT, 521B, or 521BXT added
(learned) into Zone Type 80.
The basic system may also include:
SuperBus 2000 RF Transceiver (60-821) for use with
listed wireless signaling devices.
Wireless Smoke Sensor (60-506-319.5 or 60-848-02-95)
added (learned into Zone Type 80.
SuperBus 2000 Printer Automation Module
(60-783) for use with a listed printer.
SuperBus 2000 Dual Phone Line Module (60-768) for
expansion to primary and secondary phone line reporting.
24V Smoke Loop SnapCard (60-767).
System Setup and Programming
The system Feature Numbers shall be set as follows in
UL 985 listed systems:
Household Burglar-Alarm System Units (UL 1023)
Basic system plus:
Hardwire Magnetic Contact (13-068 or 13-071)
The basic system may also include:
SuperBus 2000 RF Transceiver (60-821) for use with
listed wireless signaling devices.
Wireless Learn Mode Door/Window Sensor (60-362)
SuperBus 2000 Printer or Automation Module
(60-783) for use with a listed printer.
SuperBus 2000 Dual Phone Line Module (60-768) for
expansion to primary and secondary phone line reporting.
System Setup and Programming
The system Feature Numbers shall be set as follows in
UL 1023 listed systems:
Table 4. UL 985 Listed System Settings
Feature
No.
Feature Required Setting
xx002 Siren Time Out 4 min. minimum
xx003 Standard Entry Delay 45 sec. maximum
xx004 Exit Delay 60 sec. maximum
yy004 Communication Format 0 Contact ID
xx085 Enable Police Panic Keys 1-On
xx086 Enable Auxiliary/Medical
Panic Keys
1-On
xx087 Enable Fire Panic Keys 1-On
xx088 Report Partition/Area Events
to Central Station
1-On
xx092 Enable Auto Force Arming 0-Off
xx097 Exterior Arming Verification 0-Off
xx102 One-Time Reset Enabled 0-Off
xx108 Enable Daily Reporting of
Partition Trouble
1-On
17036 AC Stable Time 90 sec. maximum
17041 Hours to Delay Before
Reporting AC Failure
8 hours (or less)
17049 RF Supervisory Time A 4 hours
17069 No Phone Line Attached 0-Off
17072 Enable RF Jam Detect 1-On
17073 Battery Test Interval 1-4 hours
17076 Commercial or Residential
Installation
0-Off Residential
17078 Detect Receiver Failure 1-On
17079 Alarm Messages Play at High
Vo l u m e
1-On High
17096 Report System Events 1-On
47004 Zone Attributes (edit zones) N/A
xx = Two digit partition number.
yy = Two digit non-pager phone number.
Table 5. UL 1023 Listed System Settings
Feature No. Feature Required Setting
xx002 Siren Time Out 6 min. minimum
xx003 Standard Entry Delay 45 sec. maximum
xx004 Exit Delay 60 sec. maximum
yy004 Communication Format 0 Contact ID
xx088 Report Partition/Area Events
to Central Station
1-On
xx092 Enable Auto Force Arming 0-Off
xx097 Exterior Arming Verification 0-Off
xx102 One-Time Reset Enabled 0-Off
xx108 Enable Daily Reporting of
Partition Trouble
1-On
17036 AC Stable Time 90 sec. maximum
17041 Hours to Delay Before
Reporting AC Failure
8 hours (or less)
17049 RF Supervisory Time A 4 hours
17069 No Phone Line Attached 0-Off
17072 Enable RF Jam Detect 1-On
17073 Battery Test Interval 1-4 hours
17076 Commercial or Residential
Installation
0-Off Residential
17078 Detect Receiver Failure 1-On
17079 Alarm Messages Play at High
Vo l u m e
1-On High
17096 Report System Events 1-On
Table 4. UL 985 Listed System Settings (Continued)
Feature
No.
Feature Required Setting

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Advent and is the answer not in the manual?

GE Advent Specifications

General IconGeneral
BrandGE
ModelAdvent
CategorySecurity System
LanguageEnglish

Related product manuals