24-May-12 Section 3. EntelliGuard
®
TU Trip Unit System
©2012 General Electric All Rights Reserved
Table 3.6. Fuse Characteristic: Nominal Clearing and Commit Times for X Multipliers of Nominal Pickup
• Algorithm will not commit below 1.5 cycles, clearing time will not be less than 0.08sec.
• Maximum LT curve is 15XLTPU for Envelope 1 and 2 devices, 10XLTPU for Envelope 3 devices.
• Actual Long Time pickup is 112% of nominal pickup.