The EntelliGuard TU Trip Unit provides a non-core CT input
for zero sequence or residual summation current. The
expected ratio is 1A = 100%.
The Neutral Rogoswki CT’s are used to measure the Neutral
Current and is required when Internal Ground Fault is
selected on the trip unit. There are two types available:
1. Encased with Terminal Screws: The Rogowski coil is
encased with two terminal screws. No additional
mounting hardware is required as the encasing is
molded to the mounting dimensions. Table 4.30
2. Loose Rogowski Coil with separate mounting
hardware: The coil and mounting hardware are
separate. The coil comes with the two wire leads
for connection to a terminal block. Table 4.30a
Table 4.30. Neutral Rogowski CTs
(Encased with Terminal Screws)
1
2
Table 4.30a. Neutral Rogowski CTs (Loose Rogowski Coil
and mounting hardware)
1
2
Sealed Door Panel Escutcheon
An optional complete IP54 front door panel is available
when a higher degree of protection is needed (Table 4.31).
Mechanical Operations Counter
Used with either manual or motor charged circuit breakers,
the counter provides an accurate record of the cumulative
number of complete breaker closing operations (Table 4.31).
Table 4.31. Miscellaneous Accessories
IP54 Door Panel - Withdrawable Type
IP54 Door Panel - Fixed Pattern
Mechanical Operations Counter
• Contact factory for availability.
See Table 4.32.
Table 4.32. Door Interlocks