DET-653C EntelliGuard
®
G Circuit Breaker Application Guide
24-May-12 Section 5. Catalog Numbering Guide
©2012 General Electric All Rights Reserved
EntelliGuard
®
G Power Circuit Breaker
Section 5. Catalog Numbering Guide
EntelliGuard G ANSI/UL489 Circuit Breaker Catalog Number Guide
Circuit Breaker Family
Breaker Switch Type
Current Rating Sensors
Short Circuit Withstand Rating
Mounting
Spring Charge Motor
Closing Devices
Shunt Trip
UVR
2nd Shunt Trip, 2nd UVR
Auxiliary Switch, Coil Signaling
Contact
Bell Alarm, Mechanical Counter,
Trip Annunciation
Key Interlock and Padlock
Device
Mechanical Interlock
Overcurrent Protection Ground
Fault
ZSI
Advanced Features and
Communications
Rating Plug
Digit 1 – Circuit Breaker Family
EntelliGuard G Breaker/Switch
Breaker/Switch Type,
Secondary Mounting
ANSI/UL1066 Circuit
A N A
ANSI Non-auto CB
C M C
UL489 Non-auto CB
D S D
• Top = Top Mounted Secondary Disconnects (TSD).
• Side = Side Mounted Secondary Disconnects (SSD). (Available on Envelope
1 only.)
• N, U, M, S characters are for Envelope 1 only with top mounted
secondary disconnects (TSD).
• When ordering codes A, B, C, D, Side Secondary Disconnects (SSD) are
supplied as standard on Envelope 1.
• Codes N, U, M, S are not valid for Envelopes 2 & 3.
• Envelope 1 (Type N and H, 400A - 2000A).
• DC Ratings; trip unit not included. DC Rated Circuit Breakers require
external control devices (e.g., Type 37 or Type 76 DC Relays).
• Side Secondary Disconnects are specifically intended for 5-High ("high
density") equipment designs.
• With Side Mounted Disconnects (SSD), the following aux switches are not
valid (In Digit 12); Auxiliary Switch, 8 NO+8 NC (Power Rated) or Aux.
Switch, 4 NO/4 NC (Power Rated) + 4 NO/4 NC low signal (Hi-Fi).
Digits 3 & 4 – Current Rating/Sensors
Current Sensor
Rating (A)
*Switches (Digit 2 = M, S, C, D) do not have current Sensors or a trip unit.