DET-653C EntelliGuard
®
G Circuit Breaker Application Guide
24-May-12 Section 4. Accessories
©2012 General Electric All Rights Reserved
Table 4.14. Power Rated (4NO/4NC) + Low Signal (Hi-Fi) (4NO/4NC) (Ref Drawing 10099234)
PL1
PL5
PL2
PL6
PL4
PL8
PL3
PL7
• 15A max. current, 440V max.
Circuit Breaker - Key Interlock Facility
This option supplies factory-installed key interlock
mounting provisions (baseplates and mechanism) on the
front of the breaker fascia. Key interlocks ensure that a
circuit breaker cannot be closed unless the dedicated key
has been inserted and secured within the lock. Circuit
breakers accept ready-to-fit interlocking device kits such
as Castell, Ronis, Kirk and Profalux for installation
between related, separate circuit breakers. NOTE: Locks
and keys are not supplied by GE. Please order separately
from your local supplier (Table 4.15 and Figs. 4.3 and 4.4).
Table 4.15. Key Interlocks and Door Interlocks
Baseplate and mechanism for Ronis locks
GBRONR
Baseplate and mechanism for Kirk Key locks
GBKRKR
Mechanism for Ronis key cassette interlock
GCRONR
Mechanism for Kirk key cassette interlock
GCKRKR
Door interlock (left side)
Door interlock (right side)
• Kirk Keys for Fixed Breaker: CN22. Kirk Keys for Cassette:
KCAMXXX105 (Extended), KCAMXXX11S (Withdrawn). S
indicates that the key designation (A,B, etc.) is to be
stamped on the lock and the key.
• Ronis: Type 1104B lock with standard key, 1/4 in. turn to
trap the key, compulsory spindle size.
• For drawout breaker applications, key interlocks can be
mounted in the cassette.
Figure 4.3. Breaker-Mounted Key Interlock
A Key interlock mounting locations
Figure 4.4. Cassette-Mounted Key Interlock