DET-653C EntelliGuard
®
G Circuit Breaker Application Guide
24-May-12 Section 4. Accessories
©2012 General Electric All Rights Reserved
Figure 4.35. Terminations for DC Switches UL 489B
The remote racking operator allows the user to move a draw
out circuit breaker between the CONNECT and DISCONNECT
positions via an electric racking gear head motor and the
Cassette housing the breaker. The remote racking operator
requires 115VAC, 60Hz control power. A control box
connected to the operator with a thirty-foot chord permits
control from a remote location.
Grounding/Earthing Device (IEC Only)
All EntelliGuard G circuit breakers can be fitted with a
grounding/earthing device, which has a short circuit rating
equal to the breaker withstand rating. This permits either the
feeder cables or the busbar to be safely grounded and
locked during system maintenance operations (Table 4.36).
Table 4.39. Earthing Devices (IEC only)
1
2
3
A factory-installed rejection feature prevents mismatching
breakers and cassettes/substructures. This prevents (a)
inserting a breaker with a lower rating into a higher rated
cassette/substructure and (b) inserting a higher rated
breaker into a lower rated cassette/substructure. Mis-
insertion Interlock catalog number is GREPM.