DET-653C EntelliGuard
®
G Circuit Breaker Application Guide
24-May-12 Section 4. Accessories
©2012 General Electric All Rights Reserved
47
Bell Alarm with Lockout
The Bell Alarm provides remote indication that the circuit
breaker has opened because of an electrical fault. The
Lockout feature is integral to the trip unit. When a Bell Alarm
is supplied with the breaker, the Trip Unit dial is set and
locked to the manual position. In order to re-close the
breaker, the Lockout button must be pushed in/reset on the
Trip Unit 1-Form C contact (Tables 4.21 and 4.22).
Table 4.21. Bell Alarm Switches
Switch Configuration
Cat. No.
One single pole, double throw switch
(1-Form C contact)
GBAT1R
Table 4.22. Bell Alarm Ratings (Common 1 NO/NC
Contact Configuration)
Ratings
AC
120Vac
6A
250Vac
6A
DC
125Vac
0.5A
250Vac
0.25A
Charging Spring Status Indicator
Factory-installed on the motor, this auxiliary switch indicates
that the circuit breaker is charged and is standard with the
spring-charging motor (Table 4.23).
Table 4.23. Spring Charged Contact (1 NO)
Ratings
Catalog Number
AC
120Vac
6A
GSCC1R
250Vac 6A
DC
125Vdc 0.5A
250Vdc
0.25A
Secondary Disconnects (Factory-installed/Field
Installable)
Inputs and outputs to the circuit breaker are wired through
secondary disconnects located on either the top or the side
(Envelope 1 only) of the breaker. The plug-style secondary
disconnects engage mating disconnects in the breaker
cubicle when the breaker is in the TEST or CONNECT position.
Up to 78 points are available so that all breaker accessories
can be wired to dedicated disconnect points (Tables 4.24
through 4.29). Block B is ordered separate for cassettes, Cat.
No. GSDWTR.
Table 4.24. Secondary Disconnect Block Locations
Top Disconnect
Block B
Block A
Side Disconnect
Block A
circuit breaker/cradle
viewed from the front
Block B
Table 4.25. Wiring Schematic for Block-A (Three Layer Secondary Disconnect with Basic GTU and Basic Accessories)
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
A11
A12
A13
Motor Motor
Spr NO/
RTC NO
Spr NO/
RTC NO
ST1 ST1 UV1 UV1 CC COM CC IMM CC CMD
ST2/
UV2
ST2/
UV2
Max. Current (I)
14.8A
14.8A
10A
10A
1.9A
1.9A
1.9A
1.9A
1.9A
1.9A
1.9A
1.9A
1.9A
Max. Voltage (V)
440V
440V
240V
240V
440V
440V
440V
440V
440V
440V
440V
440V
440V
A14
A15
A16
A17
A18
A19
A20
A21
A22
A23
A24
A25
A26
NC3 NC3 NC2 NC2 NC1 NC1 NO3 NO3 NO2 NO2 NO1 NO1 -
Max. Current (I)
15A
15A
15A
15A
15A
15A
15A
15A
15A
15A
1A
15A
-
Max. Voltage (V)
440V 440V 440V 440V 440V 440V 440V 440V 440V 440V 440V 440V -
A27
A28
A29
A30
A31
A32
A33
A34
A35
A36
A37
A38
A39
O/P1a O/P1b O/P2a O/P2b 24 V+ 24 V- BA NC BA NO BA COM N-RC- N-RC+ Eleg-CT Eleg-CT
Max. Current (I)
1A 1A 1A 1A <500mA <500mA 10A 10A 10A <50mA <50mA 5A 5A
Max. Voltage (V)
30Vdc/
25Vac
30Vdc/
25Vac
30Vdc/
25VAC
30Vdc/
25Vac
30V 30V 240V 240V 240V 480mV 480mV 2V 2V