EasyManua.ls Logo

GE EntelliGuard G - Entelliguard TU Trip Unit for Entelliguard G Breaker

GE EntelliGuard G
94 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DET-653C EntelliGuard
®
G Circuit Breaker Application Guide
24-May-12 Section 5. Catalog Numbering Guide
©2012 General Electric All Rights Reserved
70
EntelliGuard TU Trip Unit for EntelliGuard G Breakers
Sample
GG
M
16
L4
X
6
A
XXXX
Digit
1&2
3
4&5
6&7
8
9
10
11-14
EntelliGuard Trip Unit Form
Frame Rating
Sensor Rating
Overcurrent Ground Fault
Protection
ZSI
Adv. Features and Comm.
Manual Auto Trip Reset
Future Use
Digit 1 & 2 Trip Unit Form/Family
Circuit Breaker Type
Code
Power Break 1 (UL)
GA
Power Break 2 (UL)
GB
AKR (ANSI)
GC
WP (ANSI)
GW
Mpact Low (IEC)
GL
Mpact 24-48V (IEC)
GH
Mpact 120-240V (IEC)
GQ
Entelliguard G ACB (ANSI)
GG
Entelliguard G ACB (UL)
GU
Entelliguard G ACB (IEC)
GT
EntelliGuard G Universal Spare Trip
G1
Type A Conversion Kits (ANSI)
G2
Entelliguard G Switch (IEC)
G3
This Application Guide documents the EntelliGuard TU Trip Unit for
EntelliGuard G Circuit Breakers.
GE Legacy ANSI, UL Circuit Breakers are documented in DEH-4567.
Digit 4 & 5 Sensor Rating
Sensor Rating
Code
UNIV*
00
400
04
600**
06
800
08
1000**
10
1200**
12
1600
16
2000
20
2500**
25
3000**
30
3200***
32
4000
40
5000
50
6000**
60
*Universal Spare Trip Unit.
**UL only.
***ANSI only.
Digit 3 EntelliGuard G Frame Rating
Code
240V
480V
600V
1/2S Withstand
HSIOC
Override No 1
Override WI
Interrupting Rating Tier, ANSI/UL1066 Devices LVPCB
S
65,000
65,000
50,000
50,000
50,000
49,000
53,500
N
65,000
65,000
65,000
65,000
none
none
none
H
85,000
85,000
65,000
65,000
65,000
63,700
69,550
P
100,000
100,000
65,000
65,000
65,000
63,700
69,500
E
85,000
85,000
85,000
85,000
none
none
none
M
100,000
100,000
85,000
85,000
85,000
83,300
90,950
B
100,000
100,000
100,000
100,000
none
none
none
L
150,000
150,000
100,000
100,000
100,000
98,000
107,000
Interrupting Rating Tier, UL489 Devices ICCB
S
65,000
65,000
50,000
42,000
42,000
N/A
44,940
N
65,000
65,000
65,000
42,000
42,000
N/A
44,940
H
85,000
85,000
65,000
50,000
50,000
N/A
53,500
P
100,000
100,000
65,000
50,000
50,000
N/A
53,500
M
100,000
100,000
85,000
65,000
65,000
N/A
69,550
L
150,000
150,000
100,000
85,000
85,000
N/A
90,950
Refer to GEH-4567 for other circuit breaker types.
Codes E and B are for ANSI EntelliGuard G circuit breakers only.

Table of Contents