EasyManua.ls Logo

GE EntelliGuard G - Table 1.3. ANSI;UL1066 Ratings

GE EntelliGuard G
94 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DET-653C EntelliGuard
®
G Circuit Breaker Application Guide
24-May-12 Section 1. Introduction
©2012 General Electric All Rights Reserved
2
Table 1.3. ANSI/UL1066 Ratings
Interrupting Rating Tier ANSI/UL1066 Devices, LVPCB
Envelope 1
Envelope 2
Envelope 3
Type
254V
508V
635V
1/2S
Withstand
400,
800,
1200
400, 800,
1600,
2000
3200
400-3200
3200
4000-
5000
S
65,000 65,000 50,000 50,000 X
N
65,000
65,000
65,000
65,000
X
X
H
85,000
85,000
65,000
65,000
X
P
100,000
100,000
65,000
65,000
X
E
85,000
85,000
85,000
85,000
X
M
100,000
100,000
100,000
85,000
X
X
B
100,000
100,000
100,000
100,000
X
X
L
150,000
150,000
100,000
100,000
X
X
Table 1.5. Non-Automatic Circuit Breaker ANSI Version Ratings
Envelope
Type
Amps
Rated
Interrupting
Rated Endurance
Current
Minimum
Mechanical
Minimum
Electrical
Minimum
Electrical
Endurance
Endurance
at 480V
Endurance
at 600V
1
S
800
42
12,500 10,000 7,500
1
N
800
42
12,500
10,000
7,500
1
N
1600
42
12,500
10,000
7,500
1
N
2000
42
12,500
7,500
5,000
2
M
3200
65
5,000
5,000
5,000
3
B
4000
100
5,000
3,000
2,000
3
B
5000
100
5,000
2,000
1,500
GE internal quality testing requirements exceeded 20,000 mechanical and electrical operations.
Table 1.4. UL489 Ratings
Interrupting Rating Tier UL489 Devices, ICCB
Envelope 1
Envelope 2
Envelope 3
Type
240V
480V
600V
1/2S
Withstand
400-
1200
400-
2000
2500-
3000
400-
3000
3000
4000
5000-
6000
S
65,000
65,000
50,000
42,000
X
N
65,000 65,000 65,000 42,000
X
X
H
85,000 85,000 65,000 50,000
X
X
P
100,000
100,000
65,000
50,000
X
M
100,000 100,000 100,000 65,000
X
X X
L
150,000 150,000 100,000 85,000
X X X